Compact DC powered APB controllers provide 12 I/O points: 8 inputs and 4 outputs.
The 8 inputs may be used as digital or analog (0-10 Vdc) inputs. The 4 outputs may be relay or solid state (SINK or SOURCE).
The LCD Graphics Human-Machine Interface (HMI) display/keypad provides up to 64 user defined display screens. Values and alarm conditions may be displayed and the operator may enter new parameters using a flexible 8 function keypad (+, -, Up, Down, Left, Right, OK, Esc). Four of the keys provide 'soft' user programable function keys.
8 inputs
State | Condition |
OFF | < 5 Vdc |
ON | > 10 Vdc |
Analog | 0 - 10 Vdc, 250 ohm impedance |
4 Outputs
| PNP (SOURCE) |
Resistive Load | 80 Vdc, 2 Amp |
Inductive Load | |
Power: 85-240 Vac, 5 W