DC powered APB Expansion units provide
22 I/O points: 14 inputs and 8 outputs. Up to 7 DC powered expansion
units may be connected to a DC powered controller.
The 8 outputs may be relay or solid state
(SINK or SOURCE).
14 inputs
State
Condition
OFF
< 5 Vdc
ON
> 10
Vdc
8 Outputs
Relays
NPN
(SINK)
PNP
(SOURCE)
Resistive
Load
240 Vac, 10
Amp
80 Vdc, 2 Amp
80 Vdc, 2
Amp
Inductive
Load
240 Vac, 2
Amp
Power
Voltage
12-24 Vdc
Relay
5 Watt
Sink/Source
2 Watt
NOTE: It is not possible to mix AC and DC powered
units. An DC powered expansion unit must be used with an DC powered
controller.